Trigeneration plant in Damm – El Prat
DAMM, S.A.
The trigeneration plant, designed in simple cycle configuration with a 10.3 MW gas turbine (on site), has a heat recovery steam generator (HRSG) designed for the production of 17 t/h of steam, a double effect absorption chiller for cold water production, with a maximum cold power of 1,500 kW, and a steam accumulation system with floating pressure between 8 and 23 bar(g). 3 y una capacidad útil de 80 m3 de agua saturada que permite aportar 5.3 t/h de vapor adicionales en momentos de demanda máxima.